Table 17.4 Facilities—XXXX-YYYY
Compressor
cooling plant
Fluid and working
temperature ( C)
Cooling
power (kW)
Electric
power (kW)
Rated
COP
Water 8 C
Chiller 1, 2, 3
2,400
600
4
Total
2,400
600
4
Chilled water pumps
(10 pumps, 15 kW each)
150
Cooling tower water
pumps and fans
Fluid
Pump electric
power(kW)
Fan electric
power (kW)
Pump tower no 1
Water
8
10
Pump tower no 2
Water
15
20
Pump tower no 3
Water
6
10
Pump tower no 4
Water
18
20
Total
47
60
kWh/Sm 3
Compressed air plant
Pressure (MPa)
Electric
power (kW)
Inlet air flow
(Sm 3 /h)
Air compressor no 1
0.70
150
1,378
0.11
Air compressor no 2
0.70
110
1,164
0.09
Total
260
2,542
0.10
Vacuum plant
Pressure (MPa)
Electric
power (kW)
Vacuum pumps
(3 pumps, 10 kW each)
30
Total
30
Rated air flow (m 3 /h)
HVAC-UTA
Electric
power (kW)
Zone
identification
Factory zone a
60,000
15
Factory zone b
15,000
10
Factory zone c
17,000
10
Factory zone d
60,000
15
Factory zone e
20,000
10
Factory zone f
4,000
5
Total
176,000
65
Surface (m 2 ) W/m 2
Lighting
Number of lamps
Electric
power (kW)
Fluorescent lamps
36 W (indoor)
2,000
72
10,000
7.2
Discharge lamps
(outdoor)
20
4.0
2,000
2.0
Total
2,020
76
Boiler plant
Thermal power (kW)
Fluid
Input fuel
Boiler 1, 2, 3
1,500
Steam
Natural gas
Hot water 60 C Natural gas
Boiler 4
1,500
Total
3,000
Other equipment
-
-
All values are rated value
Search WWH ::