Civil Engineering Reference
In-Depth Information
10.4
Comparison Between Dissipative
and Non-dissipative Regulation Methods
An example of procedures for comparing some regulation methods is given below.
The details of the calculations are set out in Sect. 10.6 .
Figure 10.9 shows the situations to compare. The load curve is given together
with characteristic pump curves (see Fig. 10.10 ), corresponding to a fixed
speed (in this figure it is 3,550 r/min). The design working point is shown as
A n ( q n ; H n ; η n ).
A reduction of the design flow rate to 50 % is required. The working point should
move from point A n to A 1 ( q 1 ¼
0.5
q n ; H 1 ;
η 1 ) always along the load curve to
reach the new working condition.
Two alternative procedures are considered:
• Use of a dissipative regulation that modifies the load curve at constant speed by
introducing a throttling valve. The new working point
is now point
A 2
η 2 ) with the same flow as point A 1 but with increased
head. This head increase corresponds to a required shaft power:
( q 2 ¼
0.5
q n ; H 2 ;
Fig. 10.9 Working points with dissipative and non-dissipative regulation (see the example in
Sect. 10.6 )
Search WWH ::




Custom Search