2.2.2.2
Example: Calculation of Wind Loads - Building #1
Wind load calculations for the main wind-force resisting system of Building #1 (3-story pan joist framing) are
summarized below.
Wind-force resisting system: Beam and column framing:
(1)
Wind load data
Assuming the building is classified as closed (ASCE 6.5.9) and located in hurricane prone region.
Basic wind speed V = 145 mph
ASCE Figure 6-1
Occupancy category II
ASCE Table 1-1
Exposure category D
ASCE 6.5.6.3
Wind directionality factor K d = 0.85
ASCE Table 6-4
Importance factor I = 1
ASCE Table 6-1
Topographic factor K zt = 1
ASCE 6.5.7
Gust effect factor G = 0.85
ASCE 6.5.8
External pressure coefficient C p
ASCE Figure 6-6
Windward - both directions C p = 0.8
Leeward - E-W direction (L/B = 150/90 = 1.67) C p = -0.37
N-S direction (L/B = 90/150 = 0.6)
C p = -0.5
Design pressures calculations for wind in N-S direction are summarized in Table 2-3
Table 2-3 Design Pressures for N-S Direction
Height
above
ground
level, z
(ft)
Windward
design
pressure
q z GC p
(psf)
Leeward
design
pressure
q h GC p
(psf)
Total
design
pressure
(psf)
Level
K z
q z
(psf)
Roof
39
1.216
55.7
37.8
-23.7
61.5
2
27
1.141
51.9
35.3
-23.7
58.9
1
15
1.030
47.1
32.1
-23.7
55.7
(2)
Summary of wind loads
N-S & E-W directions (conservatively use N-S wind loads in both directions):
Interior frame (30 ft bay width)
Roof
= 12 kips
2nd
= 23.1 kips
1st
= 21.7 kips
Note: The above loads were determined using design wind pressures computed at each floor level.