Civil Engineering Reference
In-Depth Information
2.2.2.1
Example: Calculation of Wind Loads - Building #2
For illustration of the ASCE procedure, wind load calculations for the main wind-force resisting system of
building #2 (5-story flat plate) are summarized below.
Wind-force resisting system:
Alternate (1) - Slab and column framing with spandrel beams
Alternate (2) - Structural walls
(1)
Wind load data
Assuming the building is classified as closed (ASCE 6.5.9) and located in Midwest in flat open terrain.
Basic wind speed V = 90 mph
ASCE Figure 6-1
Occupancy category II
ASCE Table 1-1
Exposure category C
ASCE 6.5.6.3
Wind directionality factor K d = 0.85
ASCE Table 6-4
Importance factor I = 1
ASCE Table 6-1
Topographic factor K zt = 1
ASCE 6.5.7
Gust effect factor G = 0.85
ASCE 6.5.8
External pressure coefficient C p
ASCE Figure 6-6
Windward - both directions
C p = 0.8
Leeward - E-W direction (L/B = 120/60 = 2)
C p = -0.3
N-S direction (L/B = 60/120 = 0.5)
C p = -0.5
Velocity pressure exposure coefficients K z (ASCE 6.5.6.6) at various story heights are summarized in Table 2-1
Velocity pressure q z = 0.00256K z K zt K d V 2 I
ASCE 6.5.10
Design wind pressure p z = q z GC p
ASCE 6.5.12.2
(2)
Design wind pressure in the N-S Direction
Table 2-2 contains a summary of the design pressures calculations for wind in N-S direction.
Table 2-2 Design Pressures for N-S Direction
Height
above
ground
level, z
(ft)
Windward
design
pressure
q z GC p
(psf)
Leeward
design
pressure
q h GC p
(psf)
Total
design
pressure
(psf)
Level
K z
q z
(psf)
Roof
63
1.148
20.2
13.8
-8.6
22.4
4
51
1.098
19.4
13.2
-8.6
21.8
3
39
1.038
18.3
12.4
-8.6
21.0
2
27
0.961
16.9
11.5
-8.6
20.1
1
15
0.849
15.0
10.2
-8.6
18.8
Search WWH ::




Custom Search