Design for Shear :
V
u
at distance d from column face = 106.1 - w
u
(1.42) = 97.0 kips
where
w
u
= 1.2(3.9) + 1.6(1.1) = 6.4 klf
(
φ
V
c
+
φ
V
s
)
max
= 0.48 b
w
d = 0.48(36)17 = 293.8 kips > 97.0 kips O.K.
φ
V
c
= 0.095 b
w
d = 0.095(36)17 = 58.1 kips
φ
V
c
/2 = 29.1 kips
Length over which stirrups are required = (106.1 - 29.1)/6.4 = 12.0 ft
φ
V
s
(required) = 97.0 - 58.1 = 38.9 kips
Try No. 4 U-stirrups
From Fig. 3-4, use No. 4 @ 8 in. over the entire length where stirrups are required.