The SDC can be determined based on Table 11.6-1 and the building assigned SDC A. This will reduce the
seismic forces drastically. For illustrative purposes only this building example will continue using SDC B.
Table 11-1 shows that the building frame system with ordinary frame can be used for SDC B.
Fundamental Period
The approximate natural period of the structure can be calculated as follows:
T = C
t
h
n
x
For moment resisting frame system C
t
= 0.016 and x = 0.9
T = 0.016(39)
0.9
= 0.43 second (also T can be obtained from Fig. 11-8)
Seismic Response Coefficient:
S
D1
R
I
C
s
=
⎛
⎜
⎞
⎟
T
For ordinary moment resisting frame system the modification factor R = 3 Table 11-1 (ASCE Table 9.5.2.2).
The occupancy importance factor I
E
= 1 (2003 IBC Table 1604.85).
0.11
3
1
C
s
=
0.43
=
0.087
⎛
⎞
⎜
⎟
C
s
should not be taken less than:
C
s
= 0.01
C
s
need not exceed:
S
DS
R
I
0.16
3
1
C
s
=
=
=
0.053
⎛
⎜
⎞
⎟
⎛
⎞
⎜
⎟
Use
C
s
= 0.053