Civil Engineering Reference
In-Depth Information
c
w =
ω+α
β 1 ,whereβ 1 = 0.85 for
f c = 4000psi
ʹ
2
ω+
0.85
f y
ʹ
A st
w h
ω=
f c
P u
w h
α=
f c
ʹ
h = thickness of wall, in.
φ
= 0.90 (strength primarily controlled by flexure with low axial load)
Note that this equation should apply in a majority of cases since the wall axial loads are usually small.
6.5.1
Example: Design for Flexure
For Alternate (2) of Building #2 (5-story flat plate), determine the required amount of moment reinforcement
for the two shearwalls. Assume that the 8 ft wall segments resist the wind moments in the E-W direction and
the 20 ft-8 in. wall segments resist the wind moments in the N-S direction.
Roof:
DL = 122 psf
Floors:
DL = 142 psf
(1) Factored loads and load combinations
When evaluating moment strength, the load combination given in ACI Eq. (9-6) will govern.
U = 0.9D + 1.6W
(a) Dead load at first floor level:
Tributary floor area = 12
40 = 480 sq ft/story
Wall dead load = (0.150
3392)/144 = 3.53 kips/ft of wall height (see Sect. 6.3.1)
P u = 0.9[(0.122
480) + (0.142
480
4) + (3.53
63)] = 498 kips
Proportion total P u between wall segments:
2-8 ft segments:
2
96 = 192 in.
192/440 = 0.44
1-20 ft-8 in. segment:
248 in.
248/440 = 0.56
For 2-8 ft segments:
P u = 0.44(498) = 219 kips
1-20 ft-8 in. segment
P u = 0.56(498) = 279 kips
96"
(b) Wind moments at first floor level:
 
Search WWH ::




Custom Search