Civil Engineering Reference
In-Depth Information
6.4.2
Example 2: Design for Shear
For Alternate (2) of Building #2 (5-story flat plate), select shear reinforcement for the two shearwalls. Assume
that the total wind forces are resisted by the walls, with slab-column framing resisting gravity loads only.
(1) E-W direction
Total shear force at base of building (see Chapter 2, Section 2.2.2.1):
V = 6.9 + 13.4 + 12.9 + 12.2 + 12.6 = 58 kips
For each shearwall, V = 58/2 = 29 kips
8" typ.
V u = 46.4 kips
8'-0"
Factored shear force (use ACI Eq. (9-4) for wind load only):
V u = 1.6(29) = 46.4 kips
For the E-W direction, assume that the shear force is resisted by the two 8 ft flange segments only. For
each segment:
φ
V c = 7.3
8 = 58.4 kips
(see Table 6-5)
Since V u for each 8 ft segment = 46.4/2 = 23.2 kips which is less than
V c /2 = 58.4/2 = 29.2 kips, provide
minimum wall reinforcement from Table 6-2 For 8 in. wall, use No. 4 @ 12 in. horizontal reinforcement
and No. 3 @ 11 in. vertical reinforcement.
φ
(2) N-S direction
Total shear force at base of building (see Chapter 2, Section 2.2.2.1):
V = 16.2 + 31.6 + 30.6 + 29.2 + 30.7 = 138.3 kips
For each shearwall, V = 138.3/2 = 69.2 kips
 
Search WWH ::




Custom Search