Civil Engineering Reference
In-Depth Information
5.9
COLUMN SHEAR STRENGTH
Columns in sway frames are required to resist the shear forces from lateral loads. For members subjected to
axial compression, the concrete shear strength
V c is given in ACI Eq. (11-4). Fig. 5-17 can be used to obtain
this quantity for the square column sizes shown. The largest bar size from the corresponding column design
charts of Figs. 5-18 through 5-25 were used to compute
φ
φ
V c (for example, for a 16
×
16 in. column, the largest
bar size in Fig. 5-21 is No. 11).
ACI Eq. (9-6) should be used to check column shear strength:
U = 0.9D + 1.6W
N u = P u = 0.9D
V u = 1.6W
If V u is greater than
φ
V c , spacing of column ties can be reduced to provide additional shear strength
φ
V s . Using
the three standard spacings given in Chapter 3, Section 3.6, the values of
φ
V s given in Table 5-12 may be used
to increase column shear strength.
Table 5-12 Shear Strength Provided by Column Ties
Tie
Spacing
V s - #3 ties*
V s - #4 ties*
φ
φ
d/2
19 kips
35 kips
d/3
29 kips
54 kips
d/4
40 kips
71 kips
* 2 legs, Grade 60 bars
For low-rise buildings, column shear strength
φ
V c will usually be more than adequate to resist the shear forces
from wind loads.
5.9.1
Example: Design for Column Shear Strength
Check shear strength for the 1st floor interior columns of Building No. 2, Alternate (1) - slab and column
framing without structural walls. For wind in the N-S direction, V = 9.17 kips (see Fig. 2-17).
N u = P u = 306 kips (see Example 5.7.1)
V u = 1.6(9.17) = 14.67 kips
From Fig. 5-17, for a 16
×
16 in. column with N u = 306 kips:
φ
V c 32 kips > 16.42 kips O.K.
Column shear strength is adequate. With No. 10 column bars, use No. 3 column ties at 16 in. on center (least
column dimension governs; see Table 5-3).
Search WWH ::




Custom Search