Table 5-1 1 Edge Column Load Summary for Building #1
ACI Eq. (9-3 )
Floor
ACI Eq. (9-2)
ACI Eq. (9-4)
ACI Eq. (9-6)
P
M
P u
M u
P u
M u
P u
M u
3rd
64
202
71
233
66
223
48
166
2nd
165
164
140
150
154
194
109
150
1st
262
164
220
169
247
232
176
188
(3) COLUMN SIZE AND REINFORCEMENT
For edge columns, initial selection of column size can be determined by referring directly to the column design
charts and selecting an initial size based on required moment strength. For largest M u = 233 kips, try a 16
×
16
in. column (see Fig. 5-21).
Check for fire resistance: From Table 10-2, for fire resistance ratings of 1 hour and 2 hours, minimum column
dimensions of 8 in. and 10 in., respectively, are both less than 16 in. O.K.
Determine if the columns are slender.
Using k = 1.2, slenderness ratios for all columns:
(
) − 19.5
1.2 13
×
12
k
u
r
=
=
34
>
22
()
0.3 16
Thus, all of the columns are slender. To neglect slenderness effects, the size of the column would have to be:
(
) − 19.5
1.2 13
×
12
<
22
h
>
24.8in.
0.3h
This column would probably not be practical for a building of the size considered.
Fig. 5-16 shows the results from spColumn for a first story edge column, including slenderness effects. Thirty
five percent of the gross moment of inertia was used for the 36
19.5 in. column-line beam and seventy
percent of the gross moment of inertia of the column cross section to account for cracking. The column was
assumed fixed at the foundation. As can be seen from the figure, 8-No. 11 bars are required in this case.
×
Check for fire resistance: From Table 10-6, for fire resistance ratings of 4 hours or less, required cover to main
longitudinal reinforcement is 1.5 in. < provided cover = 1.875 in. O.K.