Example: Design of an Interior Column Stack for Building #2 Alternate (2) -
Slab and Column Framing with Structural Walls (Non-sway Frame)
f c
ʹ
= 4000 psi (carbonate aggregate)
f y = 60,000 psi
Required fire resistance rating = 2 hours
For the Alternate (2) framing, columns are designed for gravity loading only; the structural walls are designed
to resist total wind loading.
(1) LOAD DATA
Roof:
LL = 20 psf Floors: LL = 50 psf
DL = 122 psf
DL = 142 psf (9 in. slab)
Calculations for the first story interior column are as follows:
(a) Total factored load (see Table 5-7):
Table 5-7 Interior Column Gravity Load Summary for Building #2, Alternate (2)
Floor
Dead
Load
(psf)
Live
Load
(psf)
Tributary
Area
(sq ft)
Influence
Area
(sq ft)
RM
Reduced
Live Load
(psf)
Cumulative
Dead Load
(kips)
Cumulative
Live Load
(kips)
Cumulative
Factored
Load ACI-
Eq. (9-2)
(kips)
5 th (roof)
122
20
480
--
1
20
63
9.6
80
4 th
142
50
480
1920
0.59
29.5
135
23.76
189
3 rd
142
50
480
3840
0.49
24.5
207
35.52
295
2 nd
142
50
480
5760
0.45
22.5
279
46.32
398
1 st
142
50
480
7680
0.42
21
351
56.4
501
(b) Factored gravity load moment:
M u = 0.035 q Lu ˜ 2 ˜ n 2 = 0.035(1.6 x 0.05)(24)(18.83 2 ) = 23.8 ft-kips
portion of M u to 1st story column = 24 (12/27) = 10.6 ft-kips
Similar calculations can be performed for the other floors.