Civil Engineering Reference
In-Depth Information
Refer to Table 4-7:
b 1 = b 2 = 16 + 9.5 = 25.5 in. = 2.13 ft
A c = 4(25.5)
9.5 = 969 in. 2
J/c = [25.5
9.5(25.5
4) + 9.5 3 ] /3 = 8522 in. 3
V u = (84,700/969) + (0.4
178.5
12,000/8522)
= 87.4 + 100.5 = 187.9 psi < 215 psi
Note that the shear stress around the drop panel is much less than the allowable stress (calculations not
shown here).
With drop panels, a lesser slab thickness for deflection control is permitted. From Table 4-1 (flat slab with
spandrel beams): h = ˜ n /36 = (22.67
12) /36 = 7.56 in. could possibly reduce slab thickness from 8 1 2 to 8
in.; however, shear strength may not be adequate with the lesser slab thickness. For this example hold the
slab thickness at 8 1 2 in. Note that the drop panels may not be required in the upper stories where the transfer
moment due to wind become substantially less (see Fig. 2-15).
Use 8 1 2 in. slab with 2 1 4 in. drop panels at interior columns of 1st story floor slab. Drop panel dimensions
= ˜ /3 = 24/3 = 8 ft. Use same dimension in both directions for economy of formwork.
Check for fire resistance: From Table 10-1 for fire resistance rating of 2 hours, required slab thickness
= 4.6 in. < 8.5 in. O.K.
3. Factored moments in slab due to gravity load (N-S direction).
(a) Evaluate spandrel beam-to-slab stiffness ratio
α
and
β t :
Referring to Fig. 4-7:
23.5"
12 + 11.5 < 12 + 4(8.5)
˜ 2 = (20
12) /2 = 120 in.
a = 20 in.
b = 12 in.
h = 8.5 in.
a/h = 20/8.5 = 2.4
b/h = 12/8.5 = 1.4
12"
f
1.37
b
2
12
120
( )
()
( ) = 1.89 > 0.8
3
3
α=
a/h
f =
24
1.37
f
Note that the original assumption that the minimum h = ˜ n /33 is O.K. since
α f > 0.8 (see Table 4-1).
β t C
8425
27,680
21 s =
) = 0.55 < 2.5
(
Search WWH ::




Custom Search