Environmental Engineering Reference
In-Depth Information
Fig. 7.14 Example from an arc furnace of a cumulative flicker power curve to determine P lt
(length exaggerated in the Figure) is
ϕ f . In the example, the angle sum is approxi-
80 . Hence the projection of Z k Δ
mately (
I on U V indicating the voltage
variation is rather small. Note that c decreases with the cosine of the angle sum and
can theoretically become zero. Regulations, however, prescribe to limit and set the
cos-value = 0 , 1if
ψ k +
ϕ f )
< 0 , 1.
Flicker coefficients vary with ratings and are generally larger for turbines with
stall control than with pitch control. For a system where c is known, the long term
flicker strength is calculated from equation (7.9) rearranged:
|
cos(
ψ kV +
ϕ f )
|
S k cos (
ϕ f )
S n
P lt = c
·
ψ kV +
Noting that for a given WES the flicker coefficient is a function of the short-
circuit impedance phase angle, the manufacturers are requested to declare c for se-
lected values of the short-circuit impedance phase angle:
S k
S n
c (
ψ k )= P lt (
ψ k )
·
(7.10)
Further, a grid-dependent switching current factor is defined which describes the
influence of the system current on voltage variations:
ψ k )= Δ
U
U
S k
S n
k i ψ (
(7.11)
In Table 7.2 characteristic values for selected systems (the same as in Table 5.1)
are collated which are relevant for flicker and switching properties; also part-load
power factors and permissible peak power values are given.
 
Search WWH ::




Custom Search