Environmental Engineering Reference
In-Depth Information
where
i
1
2
3
4
5
a i
0,0314
0,0525
0,0657
0,028
0,080
P i %
P (0,1%)
P (1%)
P (3%)
P (10%)
P (50%)
The level values are recorded in a 10 min test series, as determined from mea-
sured quantiles of the relevant cumulative value, e.g. P 10% . The long-time flicker
strength follows with N = 12 for 12
·
10 min by cubic smoothing:
3 1
12
12
1
P st , i
P lt =
(7.8)
An example of a cumulative power curve, taken from an arc-furnace (which is
the main source of flicker) is shown in Fig. 7.11. The power levels P i can be read
from the curve F ( P ), and the algorithm to determine P lt applied.
Grid regulations require the long term flicker strength not to exceed P lt = 0 , 65
on the low voltage side. The code [VDEW98] for medium voltage level requires a
tighter maximum of P lt = 0 , 46, corresponding to A lt
0 , 1.
To assess the quality of one or more generating units relating to flicker-relevant
voltage variations, a dimensionless flicker coefficient c is defined. It can be deter-
mined from tests under realistic operation conditions, alternatively declared by the
manufacturer or a test institute. When c is known, the long term flicker strength is
calculated by:
P lt = c S nG
S kV
Hence c is connected with the long-term flicker strength P lt , and the ratio of the
rated apparent power S nG of a generating unit, and S kV the short circuit power at
the point of common connection. At further inspection, determination of relative
voltage variations requires to take the relevant phase angle into account; in this case
ψ kV of the short-circuit impedance and
ϕ f , a flicker-relevant angle of the generator
unit. Coefficient c is then determined from measured values of P lt and
ϕ f of the
generator:
S kV
S nG · cos (
ϕ f )
c = P lt ·
(7.9)
ψ kV +
where
ϕ f = atan Δ
Q
Δ
P
Note that phase angles are counted from current to voltage, so that values are
> 0 for inductive impedances. Fig. 7.14 illustrates the case of an asynchronous gen-
erator, connected to an infinite bus via a short-circuit impedance Z k ; the circuit is
similar to that in Fig. 7.2a. The current vector I G for generator operation ends on the
machine's current-locus circle of which a part is shown. The tangent in the working
point is used for linearization; hence the phase angle of small current variations
Δ
I
 
Search WWH ::




Custom Search