Environmental Engineering Reference
In-Depth Information
Fig. 7.1 Model of
short-circuit impedance
between generator and grid
and voltage variation
a)
b)
The WES is modeled by the generator symbol which includes line and trans-
former impedance components between terminals and connection point, referred to
the relevant nominal voltage. In an example of a WES connected to medium volt-
age 20 kV, with a transformer 110/20 kV feeding into the distribution system, where
S k = 120 MVA referred to the 20 kV-side, the short-circuit impedance is given by:
ψ k = 51
Z k =(2 , 1 + j2 , 6)
Ω
;
|
Z k |
= 3 , 342
Ω
;
Current regulations require WES to declare a factor k ψ , of influence for switching
actions, which depends on the phase angle
ψ k of the short-circuit impedance Z k .
Consider a generator operating at an apparent power S = P + j Q , the voltage
variation at CP is approximately:
U aV = R k I P
S + X k I Q
I
S ( R
Δ
=
·
P + X
·
Q )
S
When the generator is operating at rated values, with current I N and power factor
cos
ϕ N , the relative voltage increase becomes:
u aV = Δ
U aV
U N
= Z k I N
U N
Δ
cos(
ψ kV ϕ N )
Note that the angles are in consumer system notation, where the sign of a lag-
ging current (with respect to voltage) is positive, and the sign of the ohmic-inductive
impedance Z k is positive. In Fig. 7.1b an example vector diagram is shown which re-
flects the above equation under the condition that
1. Note that in this
case U B > U V due to the case of a directly coupled asynchronous generator draw-
ing its magnetizing current component from the grid. Theoretically, in the above
example the voltage deviation would become zero when operating the generator at
ϕ
|
U B / U V
1
|
= 141 .
 
Search WWH ::




Custom Search