of genelink per hour (24 points a day). The detailed variables and related
boundary constraints can be listed as follows:
Generator
The state variables of generators are as follows:
P gni : Electrical power output (24 points a day)
δ gi ∈{
0 , 1
}
: Startup/shutdown status, where, P gnmin
F gni
F gnmax
( i =0 ,..., 23 ,n =1 ,...,N g ),
N g : Number of generator,
P gnmax : Maximum output,
P gnmin : Minimum output.
Genelink
Genelink is a kind of absorption refrigerators, which can
decrease adding fuels by inputting wasted heat energy of generator. The
state variables of genelink are as follows:
Q ggLni : Heat input values (24 points a day)
Q cgLni : Output heat values (24 points a day)
δ gli ∈{
: Startup/shutdown status, where, ( i =0 ,..., 23, n =
1 ,...,N gl , ) , ( i =0 ,..., 23, n =1 ,...,N gl , ),
0 , 1
}
N gl : Number of genelink,
Q ggLnimax : Maximum heat input values determined by output heat
values,
Q cdi : Air-conditioning load,
Q rcgLn : Rated air-conditioning output.
Heat Exchanger
The state variables of heat exchanger for heating/hot
water supply are as follows:
Heat Exchanger for Heating Q ghni : Heat energy input values (24
points a day) δ hexhi ∈{
0 , 1
}
: Startup/shutdown status, where 0
A hexhn Q ghni
Q hdi ,( i =0 ,..., 23 ,n =1 ,...,N hexh ), N hexh :Number
of heat exchanger for heating, Q hdi : Heat load, A hexhn :Coe cientsof
facility characteristics.
Heat Exchanger for Hot Water Supply Q gwi : Heat energy input values
(24 points a day) δ hexwi ∈{
0 , 1
}
: Startup/shutdown status, where,
0 ≤ A hexwn Q gwni
Q wdi , ( i =0 ,..., 23 ,n =1 ,...,N hexw ), N hexw :
Number of heat exchanger for hot water supply, Q wdi : Hot water supply
load, A hexwn : Coecients of facility characteristics.