Databases Reference
In-Depth Information
of genelink per hour (24 points a day). The detailed variables and related
boundary constraints can be listed as follows:
Generator
The state variables of generators are as follows:
•
P
gni
: Electrical power output (24 points a day)
•
δ
gi
∈{
0
,
1
}
: Startup/shutdown status, where,
P
gnmin
≤
F
gni
≤
F
gnmax
(
i
=0
,...,
23
,n
=1
,...,N
g
),
•
N
g
: Number of generator,
•
P
gnmax
: Maximum output,
•
P
gnmin
: Minimum output.
Genelink
Genelink is a kind of absorption refrigerators, which can
decrease adding fuels by inputting wasted heat energy of generator. The
state variables of genelink are as follows:
•
Q
ggLni
: Heat input values (24 points a day)
•
Q
cgLni
: Output heat values (24 points a day)
•
δ
gli
∈{
: Startup/shutdown status, where, (
i
=0
,...,
23,
n
=
1
,...,N
gl
,
)
,
(
i
=0
,...,
23,
n
=1
,...,N
gl
,
),
0
,
1
}
•
N
gl
: Number of genelink,
•
Q
ggLnimax
: Maximum heat input values determined by output heat
values,
•
Q
cdi
: Air-conditioning load,
•
Q
rcgLn
: Rated air-conditioning output.
Heat Exchanger
The state variables of heat exchanger for heating/hot
water supply are as follows:
•
Heat Exchanger for Heating
Q
ghni
: Heat energy input values (24
points a day)
δ
hexhi
∈{
0
,
1
}
: Startup/shutdown status, where 0
≤
A
hexhn
Q
ghni
≤
Q
hdi
,(
i
=0
,...,
23
,n
=1
,...,N
hexh
),
N
hexh
:Number
of heat exchanger for heating,
Q
hdi
: Heat load,
A
hexhn
:Coe
cientsof
facility characteristics.
•
Heat Exchanger for Hot Water Supply
Q
gwi
: Heat energy input values
(24 points a day)
δ
hexwi
∈{
0
,
1
}
: Startup/shutdown status, where,
0
≤ A
hexwn
Q
gwni
≤
Q
wdi
,
(
i
=0
,...,
23
,n
=1
,...,N
hexw
),
N
hexw
:
Number of heat exchanger for hot water supply,
Q
wdi
: Hot water supply
load,
A
hexwn
: Coecients of facility characteristics.